|
MORE
ABOUT COMPARISON BETWEEN NEC AND IEC CODES
No one
should trifle with the safety of personnel and equipment deployed in
areas where there are or may be flammable or explosive atmospheres.
Standards for dealing with such hazardous areas have been
established based on caution and experience. But the 1996 National
Electrical Code (NEC) was modified to incorporate International
Electrotechnical Commission (IEC) standards in addition to the
existing code. Comparison of the two methodologies shows the effects
and benefits.
In the United States two methods are now allowed: the traditional
method based on Article 500, and the new IEC method allowed for the
first time in the 1996 NEC (Article 505).
The IEC methodology was added to the NEC in the 1996 code cycle.
This has been and still is controversial. It has taken several code
cycles to get this method included into the NEC. The controversy
involves business reasons, turf protection, international politics,
and safety concerns.
Like traditional area classifications, the IEC method uses three
descriptors plus extent and temperature class to classify hazardous
areas. But it uses different terms, groupings, descriptors, and
temperature ranges. The descriptors used for the IEC method are
Class, Group, and Zone.
NEC Article 505, which defines the IEC methodology, defines only
Class I areas. Like the traditional method, the definition class is
the physical nature of the material—flammable gases, vapors, and
flammable or combustible liquids. Under Article 505, no Class II or
Class III areas are defined and therefore Article 505 cannot be
applied to these areas.
The group designator has the same definition as the traditional
method but the groupings are different (Table I). For the IEC method:
Comparison
of Groups
The
IEC method combines the traditional groups A and B into a
single group IIC, making the requirements for acetylene gas
the same as for hydrogen and other highly flammable gases.
|
Traditional
Method Groups
|
IEC
Method Groups
|
|
A
|
IIC
|
|
B
|
IIC
|
|
C
|
IIB
|
|
D
|
IIA
|
GROUP I - Covers underground mines, which in the U.S. are covered by
the Mine Safety and Health Administration (MSHA), so
GROUP I is not covered by the NEC and is not applicable;
GROUP IIC - Corresponds to the traditional method's Groups A &
B;
GROUP IIB - Corresponds to the traditional method's Group C; and
GROUP IIA - Corresponds to the traditional method's Group D.
The temperature class has the same meaning as in the traditional
method but IEC method (NEC Table 505-10(b)) does not have the T1-T6
subclasses of the traditional method (Table II).
Comparison
of Temperature Classes
|
|
|
|
|
Traditional
T1
T2
T2A
T2B
T2C
T2D
T3
T3A
T3B
T3C
T4
T4A
T5
T6
|
IEC
T1
T2
-
-
-
-
T3
-
-
-
T4
-
T5
T6
|
Temperature,
C (F)
450°C (842°F)
300°C (572°F)
280°C (536°F)
260°C (500°F)
230°C (446°F)
215°C (419°F)
200°C (392°F)
180°C (356°F)
165°C (329°F)
160°C (320°F)
135°C (275°F)
120°C (248°F)
100°C (212°F)
85°C (185°F)
|
The
IEC method has the same temperature
classes as the traditional method, but the
subclasses are omitted.
The
zone designator (Table III) has the same definition as the
traditional method's division designator, but divides the likelihood
into three probabilities (Zones 0, 1, and 2) instead of two (Division
1 and 2). Zone 0 is where the hazard is considered to be there all
the time or for long periods of time.
Comparison
of Divisions with Zones
|
|
|
Traditional
Method Divisions
Division 1
Division 1
Division 2
Non-hazardous
|
IEC
Method Zones
Zone 0
Zone 1
Zone 2
Non-hazardous
|
The
IEC method separates the traditional
Division 1 into two zones. By putting the
more hazardous conditions of Division 1
into Zone 0, the requirements for Zone 1
are relaxed.
Zone
1 is where the hazard is considered to be there under normal
conditions, including repair and maintenance activities or leakage,
or where there are operations or processes which could result in the
release of a flammable mixture and could cause a simultaneous
failure of electrical equipment. An area that is adjacent to a Zone
0 area where the hazard could be communicated to would also be
classified as Zone 1.
Note that this definition of Zone 1 is essentially the same wording
as for the traditional Division 1 definition. But the most dangerous
likelihood has been separated out. This allows the use of lesser
means in Zone 1 than in Division 1, which must cover the most
dangerous likelihood (Zone 0) in addition to the less dangerous
likelihood (Zone 1).
Zone 2 is equivalent to Division 2. Again, as in the traditional
method, by definition any area that is not classified as hazardous
is classified as non-hazardous. The extent has the same definition
as the traditional method.
The IEC method is illustrated in Figure 2. One qualification
regarding its use is that NEC Article 500-3 requires that the area
classification, wiring, and equipment selection be under the
supervision of a "qualified Registered Professional Engineer."
This requirement is a bit unusual for the process industries as most
engineers are not registered but rather work under an industry
exemption. Also, the term "qualified" is not spelled out.
While a case may be made that this is a new methodology and this
would make the application more safe, this was probably an attempt
to make the use of this methodology more difficult and thus less
attractive.
Also, the NEC Handbook (NFPA-70HB) states that it is the intent that
you do not mix and match in the application of these methodologies:
these methods are mutually exclusive. A company should not use both
methods in the same facility. The exceptions to this are that
equipment approved for the traditional area classification may be
used in the equivalent IEC area.
We now have two methodologies that we can use to classify hazardous
areas, the traditional and the IEC. This provides greater
flexibility in choosing how we classify, the equipment, and what
type of electrical installation will be provided.
[more
about IEC codes]
[more about comparison between
IEC and NEC codes]
|